Live monitoring Updated 72-hour alert levelPriority Editor: Frédéric LENQUETTE
CYBERIACKCybersecurity & AI intelligence · by Frédéric LENQUETTE
CybersecurityMajor alert

Danfoss (AK-SM, AK-SC): compromises at hundreds of supermarkets, isolate from the Internet

On the night of October 11-12, Danfoss refrigeration controllers were compromised at hundreds of supermarkets, according to the retail chains and CERT-FR. Any operator of AK-SM or AK-SC units must isolate them from the Internet.

Translated from French by AI. The original French article is the reference version.

Article illustration : Danfoss (AK-SM, AK-SC): compromises at hundreds of supermarkets, isolate from the Internet
Photo : Bdx, CC0, Wikimedia Commons

Key points

On the night of October 11-12, 2026, attackers remotely disrupted refrigeration at hundreds of supermarkets through Danfoss AK-SM and AK-SC controllers, for which CERT-FR (the French government CERT) reports “numerous compromises.” Any operator of these controllers must disconnect them from the Internet or restrict access to them immediately, then update or replace them.

The facts

  • October 11-12, 2026: the temperature of freezers and refrigerators was reportedly set to 50°C (122°F). Les Mousquetaires (Intermarché) and Coopérative U confirm the attack; E.Leclerc says “one of its suppliers” of refrigeration equipment was affected. According to Les Mousquetaires, the victim is Danfoss, which manages their refrigerated display cases (franceinfo, ICI).
  • October 13: 300 Intermarché and Netto stores and about a hundred U stores were affected, according to BFMTV, cited by Next. Infosecurity Magazine also mentions Carrefour and Monoprix stores, without confirmation from those chains.
  • October 12: alert CERTFR-2026-ALE-012 reports “numerous compromises” of Danfoss AK-SM and AK-SC series controllers.
  • October 13: according to Next, Danfoss says the affected devices are obsolete controllers (AK-SM 800, AK-SC 355) or AK-SM 800A units with outdated firmware. It recommends replacing the AK-SC 355, which is no longer sold.
  • October 12-13: the Paris prosecutor's office confirmed it has opened an investigation, assigned to the Ofac (the French office against environmental and public health harm), and reported fires starting, according to Le Monde, cited by Next. According to ICI, citing the Prime Minister's office, ANSSI (France's national cybersecurity agency) identified a vulnerability in software from a Danish company.
  • August 9, 2026: Claroty Team82 published three vulnerabilities in the AK-SM 800A: a hidden authentication mechanism that could allow bypassing the password (CVE-2025-41450), a post-authentication command injection (CVE-2025-41451) and a configuration injection (CVE-2025-41452). Claroty found 2,765 interfaces exposed to the Internet (Censys). No link to the attack has been established.
  • As of October 13: the attackers' access method is not established, and no public claim of responsibility has been made.

Impact

Operators of Danfoss AK-SM and AK-SC controllers are exposed, whatever their sector; according to ICI, ANSSI is trying to identify other affected companies. The risk is physical: fresh and frozen stock destroyed, €50,000 in losses reported by the Intermarché in Mur-de-Bretagne, and fires reported by the prosecutor's office.

Danfoss's statement points to two situations that each operator can check: end-of-life devices and outdated firmware. The AK-SM 800A vulnerabilities and the exposure of thousands of interfaces were documented two months before the attack, with no link established at this stage. Managed by the manufacturer or the refrigeration contractor, these controllers easily fall outside the IT department's inventory and patch management.

Recommendations

  1. Disconnect AK-SM and AK-SC controllers from the Internet or restrict access to them (CERT-FR), as well as any supervisor or remote-maintenance gateway for refrigeration.
  2. Search firewall logs for inbound connections to these interfaces; in case of compromise, reset the device, apply patches, change secrets and review existing accounts (CERT-FR).
  3. Upgrade AK-SM 800A units to firmware R4.3.1 or later (Claroty) and plan the replacement of AK-SM 800 and AK-SC 355 units, which Danfoss classifies as obsolete.
  4. Restrict remote access to a VPN with MFA, separate these devices from the rest of the network and change maintenance passwords, including those of refrigeration contractors.
  5. Install temperature alarms that are independent of the control system and maintain a manual recovery procedure.
  6. Add these controllers to the inventory and to maintenance contracts: versions, exposure, access accounts, update deadlines.

Method: facts verified against the sources cited below, article reviewed and approved by Frédéric LENQUETTE. Our editorial policy.

CVE entries: CVE-2025-41450 CVE-2025-41451 CVE-2025-41452

Vendor page: Danfoss · 3 exploited vulnerabilities

Share this article