Danfoss AK-SM and AK-SC: roughly 700 supermarkets compromised, restrict access
On October 12, CERT-FR reported numerous compromises of Danfoss controllers; ANSSI points to exposed interfaces and weak passwords. Operators must isolate them from the Internet.
Translated from French by AI. The original French article is the reference version.

Key points
In the night of October 11 to 12, 2026, attackers forced the defrost cycle of supermarket refrigeration systems through Danfoss AK-SM and AK-SC controllers. According to the government, roughly 700 stores are affected. According to ANSSI (France's national cybersecurity agency), interfaces exposed on the Internet and weak passwords made the attack possible. Operators must disconnect these controllers or restrict access to them without delay.
The facts
- On October 12, after the forced defrost of several hundred Intermarché, Netto, Coopérative U and Leclerc supermarkets, CERT-FR (the French government CERT) published alert
CERTFR-2026-ALE-012and said it was aware of “numerous compromises” of AK-SM and AK-SC controllers. - Danfoss told AFP that most of the affected devices are older products that no longer receive updates or patches, including the AK-SM 800 and AK-SC 355. The manufacturer says it advised replacing them long ago.
- On October 13, before Parliament, Finance Minister Roland Lescure reported roughly 700 supermarkets affected out of about 10,000, according to AP. Coopérative U counts 80 out of 2,000; some stores had to throw away products.
- The Paris prosecutor's office opened an investigation and reported fires linked to the attack, according to AFP; the case has been assigned to the OFAC (the French anti-corruption and financial crime office), according to Le Monde as cited by Next. Some stores report losses of several tens or even hundreds of thousands of euros, according to LeMagIT.
- On October 21, before the Senate's Foreign Affairs Committee, Vincent Strubel, ANSSI's director general, cited “basic security failures”: devices connected directly to the Internet, administered without particular protection, with weak passwords. He dismissed the “third-party analyses” that attributed the attack to published vulnerabilities (Public Sénat).
CVE-2025-41450, reported by Claroty, gives remote administrator access on the AK-SM 800A; it is fixed in firmware 4.2, and two other 2025 vulnerabilities in 4.3.1. Claroty counted more than 2,700 exposed AK-SM 800A interfaces. A link between these vulnerabilities and the attack has not been established. No claim of responsibility has been made public.
Impact
Operators of these controllers are exposed: large-scale retail and, according to ANSSI's director general, healthcare, which stores vaccines on similar equipment. The risk is physical and financial: destroyed products, fires.
ANSSI's reading blames poor security hygiene, not a vulnerability. Next notes that a valid login is enough to change a defrost cycle, a normal administration function. Patching is therefore not enough, and older models no longer receive patches. These controllers are often administered by a refrigeration contractor or by the manufacturer, outside the IT department's scope. Any technical equipment remotely administered by a third party deserves the same review.
Recommendations
- Disconnect AK-SM and AK-SC controllers from the network or restrict access to them; if remote administration is essential, temporarily limit it to trusted IP addresses.
- Check the accounts, passwords and defrost settings on each controller, as the alert publishes no indicators of compromise.
- If a compromise is suspected, follow the CERT-FR procedure. It includes limiting access to authorized service providers, restoring factory settings, applying patches, changing secrets, reviewing accounts and fully reconfiguring the device.
- Bring AK-SM 800A units to at least version 4.3.1 and plan the replacement of models that are no longer maintained.
- Specify in maintenance contracts who administers these controllers, from where and with which credentials. Extend this review to similar healthcare equipment.
Method: article written and verified by Frédéric LENQUETTE, sources cited below. Our editorial policy.
Share this article